Jaxxen Incorporated Logo  
Electronic Timers - Series 'K'
SPECIFICATIONS:
Operation mode :

Delay on Energise (DE). The relay
energises after set interval of time.

: Interval On (IT). The relay energises
immediately and de-energises after
set interval of time.
: Cyclic (CY). The relay energises
and de-energises in cyclic mode
with adjustable and equal ON and
OFF periods.
Supply Voltages : 12, 24, 48, 110, 240V AC, 50Hz
12, 24, 48, 110V DC
Timers to suit multi voltage from 24V
to 240V AC / DC
Supply Voltage
tolerance
: ±10%
 Power consumption : 5 VA(max.)
Time ranges : 1, 2, 5, 10, 30, 60 seconds
2, 5, 10, 30, 60 minutes
2, 5, 10, 30, 60 hours
Repeatability : 1% with fixed off time between runs.
Reset Time : Less than 100ms before timing.
15 ms after timing.
Scale range : 2% to 100%
Relay :

DPDT

 

Contact Rating : 5A at 230V AC / 28V DC resistive load
Transient protection : 120mJ energy pulse
Dielectric Strength : 1500 V AC rms for 1 minute
Temperature Range : -10°C to +60°C
Electrical life : 105operations at rated resistive load
Mechanical life : 5 x 106 operations
   
Number of Change
over contacts

Series

 

Base Configuration Mode Time range Adjustment
mode
Supply voltages
2 K B DE 10S LP 240 V AC
- - A : 11 Pin base

DE

1, 2, 5, 10, 30, 60 S (seconds)

LP - Local pot

12, 24, 48, 110, 240 V AC
- - B : 8 Pin base IT 2, 5, 10, 30 , 60 M (minutes) RP - Remote pot 12, 24, 48, 110 V DC
- - C : Screw terminal base CY 2, 5, 10, 30, 60 H (hours) FT - Fixed time M- 24V TO 240V AC / DC
 

 

                                 

Request for Information

70 Raton Road, Suite E
Milford, CT 06461
©2008 Jaxxen Incorporated